PowerMAX7 4P Cat.7 S/FTP 23AWG LSZH Dca Cable – Gray
Features
- Capable of handling the latest versions of Power over Ethernet
- Conductor sizes for PowerMAX7TM Cat.7 set at 23AWG
- LSZH jacketed 4 pair telecommunications cable
- Successful transmission at 600Mhz up to a length of 100Mtrs
- EZI-Pull 305Mtr Reel for trouble free installation
- Foil wraps act to prevent crosstalk between twisted pairs
- Braided shield helps prevent EMI/RFI & AXT from entering cable
Categories: Copper Infrastructure, Fiber Optic Infrastructure
Brand: Dintek
- Description
- Specification
- Download
Description
DINTEK PowerMAX7TM shielded Cat.7 / Class F S/FTP LSZH Dca cable is guaranteed to exceed Cat.7 specifications as set down in ISO/IEC standards. Our PowerMAX7TM solution comprises shielded Cat.7 component compliant keystones, patch cords and unloaded patch panel options, both straight and angled.
When combined with DINTEK’s shielded Cat.7 / Class F S/FTP LSZH Dca cable, an end-to-end channel exists that maximizes data throughput and provides headroom for future technologies operating to, and beyond 10 Gigabit Ethernet.
Features
- Capable of handling the latest versions of Power over Ethernet
- Conductor sizes for PowerMAX7TM Cat.7 set at 23AWG
- LSZH jacketed 4 pair telecommunications cable
- Successful transmission at 600Mhz up to a length of 100Mtrs
- EZI-Pull 305Mtr Reel for trouble free installation
- Foil wraps act to prevent crosstalk between twisted pairs
- Braided shield helps prevent EMI/RFI & AXT from entering cable
Application
- Horizontal and backbone cable / Datacenter cabling
- 10GBASE-T 10 Gigabit Ethernet
- 1000BASE-TX Gigabit Ethernet / 1000BASE-T Gigabit Ethernet
- 100BASE-TX Fast Ethernet / 10BASE-TX Ethernet
- 100VG-AnyLAN / Broadband Video / Voice / T1 / ISDN
- 10 Gigabit (600Mhz) Transmission up to length of 100Mtrs
Standards Conformance
- Performance – EN 50173-1 / ISO/IEC 11801
- Structural – EN 13501-6:2014 | IEC 61156-5 | EN 50288-10-1
- PoE capability – IEEE 802.3bt level 3 & 4 (PoE++ & 4PPoE)
- Environmental – Conforms to RoHS and REACH Directives
- Flame testing – EN 60332-1-2 | EN61034-2 | EN 60754-1/2
Independent Certification
- ETL Certification according to EN 50173-1 and ISO/IEC 11801
- CPR Reaction To Fire Classification – Dca,s2,d2,a1 as per EN 50399
Technical Specifications | |
---|---|
Construction | |
Conductor | |
Material | Pure Annealed Copper |
Wire Size | 23AWG |
Strand Type | Solid Core |
No. Of Pairs | 4P |
Insulation | |
Material | Polyethylene |
Thickness | 0.429mm +0.05 / – 0.011 mm |
Diameter | 1.42mm ± 0.05mm |
Colors | Blue/White | Orange/White | Green/White | Brown/White |
Pair Foil Wrap | Aluminum-mylar tape |
Jacket | |
Material | LSZH |
Thickness | 0.5 mm ± 0.02mm |
Diameter | 7.10mm ± 0.3mm |
Color | Gray |
CPR Reaction To Fire Classification | Dca,s2,d2,a1 |
Foil Shield | None |
Braided Shield | Tinned copper braid |
Physical Ranges | |
Jacket | |
Cold Bend Test | -20 ± 2°C x 4hrs no crack |
Min. Bending Radius | Min. 8 x Cable Diameter |
Max. Pulling Tension | 110N |
Installation Temperature | 0°C to +50°C |
Operating Temperature | -20°C to +60°C |
Electrical | |
Conductor Resistance | Max. 9.5 Ω/100m at 20°C |
DC Resistance Unbalance | Max. 2% at 20°C |
Pair-to-Ground Capacitance Unbalance | Max. 1600 pF/km at 1 kHz |
Dielectric Strength of Insulation | DC 1 KV for 1 min |
Insulation Resistance Test | Min. 5000 MΩ/Km at 20°C |
Mutual Capacitance | Max. 4.6 nF/100m at 1 kHz |
Impedance 1-100MHz | 100Ω ± 15% |
Impedance 100~200MHz | 100Ω ± 22% |
Impedance 200~600MHz | 100Ω ± 25% |
Nominal Velocity Of Propagation | 74% |
DN